Skip to main content
JOHN ZDANIS

Grounding Electrode Conductor

NEC 2020 — Table 250.66

Largest ungrounded service-entrance conductorGrounding electrode conductor
CopperAluminum or copper-clad aluminumCopperAluminum or copper-clad aluminum
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 through 350 kcmilOver 250 through 500 kcmil2 AWG1/0 AWG
Over 350 through 600 kcmilOver 500 through 900 kcmil1/0 AWG3/0 AWG
Over 600 through 1,100 kcmilOver 900 through 1,750 kcmil2/0 AWG4/0 AWG
Over 1,100 kcmilOver 1,750 kcmil3/0 AWG250 kcmil

Minimum grounding electrode conductor size for AC systems, by the size of the largest ungrounded service-entrance conductor (or equivalent area for parallel conductors).

  • Where the sole connection is to a rod, pipe, or plate electrode, the grounding electrode conductor need not be larger than 6 AWG copper or 4 AWG aluminum.
  • Where the sole connection is to a concrete-encased electrode, the grounding electrode conductor need not be larger than 4 AWG copper.
  • Where the sole connection is to a ground ring, the grounding electrode conductor need not be larger than the conductor used for the ground ring.

Source: NEC 2020 Table 250.66. Verify requirements against the locally adopted code and applicable amendments.